CIRCUIT BREAKER 16A

These circuit breakers have been developed for an intensive use in the fixed or mobile tertiary and industrial installations. The maximal capacity of the borders of connecting is of 25mm² flexible and 35mm² stiff. The power of cut in 230/400V is 10 000A following EN 60898.

SKU: GEW.92687 Categories: , , Tags: ,

Description

TECHNICAL DATA

Description
MINIATURE CIRCUIT BREAKER
Code
MT 100
No. of poles
4P
No. modules
4
Rated current
16 A
Curve
C
Rated voltage
230 – 400 V
Standard
EN 60898, EN 60947-2
Rated frequency (Hz)
50/60 Hz
Breaking capacity EN 60898 230V (Icn)
10000 A
Breaking capacity EN 60898 400V (Icn)
10000 A
Breaking capacity EN 60898 (Ics)
0.75 x Icn
Breaking capacity EN 60947-2 230V (Icu)
25 kA
Breaking capacity EN 60947-2 400V (Icu)
15 kA
Breaking capacity EN 60947-2 (Ics)
50% Icu
Insulation voltage
500 V
Rated impulse withstand voltage
4 kV
Minimum operating voltage
12V ac/dc
Maximum operating voltage
440V AC / 220V DC
Electrical endurance
10000
Mechanical endurance
20.000
Section rigid cable
<=1×35 – <=2×16 – <=1×16+2×10 mm²
Section flexible cable
<=1×35 – <=2×16 – <=1×16+2×10 mm²
Rated tightening torque
2 Nm
Operating temperature
-25 +60 °C
Stocking temperature
-40 +70 °C
Electrocod
1411
Ware number
85362010
Ware number
85362010